• Connects to remote alarm systems.
Up to 3 amps 30 volts (DC) or 2 amps 250 volts
(AC) Visual remote alarm is standard.
Audio/Visual alarm optional.
• Electrical - 115 volts (AC).
• Master shut off valves included.
• Maximum inlet pressure
220 .............................3000 PSIG
220 (CO2, N2O)............2000 PSIG
200 (Acetylene, LPG)......400 PSIG
220HL (CO2, N2O)........2000 PSIG
220HP..........................3000 PSIG
220HP (CO2, N2O)........2000 PSIG
• Maximum flow rate
220............................1200 SCFH
220 (Acetylene)............300 SCFH
220 (LPG).....................400 SCFH
220 (CO2, N2O)..............35 SCFH
220HL (CO2, N2O)........500 SCFH
220HP........................2000 SCFH
• Internal adjustable line regulator:
220 and 220HL...........30-125 PSIG
Acetylene......................0-15 PSIG
LPG..............................0-30 PSIG
220 HP......................50-200 PSIG
• Manifold outlet - 1/2” NPT.
• Relief valve outlet - 3/4” NPT.
• 1/2” brass, silver brazed headers. |

• All systems include stainless steel braided
pigtails with PTFE lined inner core except
Helium and Hydrogen systems which
have a thermoplastic inner core.
• Acetylene systems include:
300 SCFH flashback arrestor and piping.
Stainless steel braided pigtails with individual
flashback arrestors and check valves. |